Installing and Connecting the Unit
12
For more information on incident responses and relay outputs, refer to the HTML Edition Units User’s
Guide.
Warning:
The signal from the Relay Output of the unit must be used as an indicator and not for direct
control of a device.
Caution:
To prevent damage to the unit, do not exceed the voltage and current ratings for the relay
terminals.
Relay Contacts Schematics
Figure 9: Relay Contacts Schematic
The input supports opto-isolated signal for a single external device.
Signals can be sent as continuous (ON/OFF) or single pulse of predefined duration.
Note:
It is also possible to configure the relay for a Normally Closed (N/C) condition. See N/O to N/C
Relay Configuration in the Appendix for details.
Relay Output Specifications
Maximum current 1A @ 30VDC
To connect a device controller to a Relay Output of the unit:
Connect the leads from the external device controller to the respective terminal points on the
spring clamp terminal block according to your requirements (Normally Open or Normally Closed
configuration). See Connecting Leads to a Spring Clamp Terminal Block (page 18). The three
terminal points for the Relay Output are located at the bottom left of the terminal block. (See
Figure 3: trk-101 Power Connection Panel)
Connect the terminal block to the external devices connector on the power connection panel of
the unit. (See Figure 3: trk-101 Power Connection Panel)
Connect the other end of the cable to the external controller, which receives the signal from the
unit and controls/powers the external device.
3.3 Resetting the Unit
The unit can be reset as follows:
Hard Reset Using the Reset Button (page 13)
Hard Reset by Removing the Power Supply (page 13)